Upload time:2025-06-04 Publisher:安立静
An air-cooled modular chiller unit installed on the rooftop of a large hotel generated severe vibration and noise after being put into operation, causing serious discomfort in the top-floor guest rooms. To protect the hotel's image and reputation, the owner required the installation contractor to fully resolve the vibration issue.
A site investigation revealed that the original vibration isolation measure consisted only of rubber pads installed between the equipment and the concrete foundation. This solution provided limited isolation performance, allowing vibration to be transmitted through the concrete base to the floor slab. Due to the relatively low stiffness of the floor slab, forced vibration occurred, radiating structure-borne noise into the rooms.
After a careful evaluation and comparison of multiple vibration isolation solutions, the installation contractor selected ALJ-17 spring isolators. Following installation, on-site measurements conducted in the guest rooms using professional instruments confirmed that all results met relevant standards. The vibration and noise reduction performance was highly effective, earning unanimous praise from both the owner and the installation contractor.


安立静减振技术有限公司致力于 各类机电设备减振产品的研发生产,生产包括弹簧减振器、橡胶减震器、薄膜气浮减振器、气垫式减震器、钢丝绳减振器等五大类,上千种规格,广泛覆盖机电设备减振领域。同时安立静公司还提供现场检测、方案设计与产品定制等减振技术服务。
A case of vibration reduction of an air-cooled module unit on the roof of a large hotel
2026-01-28
Vibration isolation characteristics of different types of pumps
2026-01-28
What are the reasons why air dampers do not inflate?
2026-01-28
Vibration remediation case of air conditioning equipment on the top floor
2026-01-28
Installation method of membrane air flotation damper
2026-01-28
Three-coordinate, roundness meter, microscope and other precision instruments shock absorption
2026-01-28
Why do cooling towers have vibration problems?
2026-01-28
Vibration isolation design of MAU computer room pipe support
2026-01-28
Vibration damping case of diesel generator
2026-01-28
Hazards of roof equipment vibration
2024-11-11
Strictly control the quality, and the quality is guaranteed!
2024-11-04
Vehicle, ship, aviation equipment control system, medical equipment, mobile electronic instruments buffer energy absorption
Material: 304 stainless steel plywo...
查看详情
Shock and vibration control of automotive, marine, aerospace, electronic, mechanical and other equipment
Material: stainless steel wire rope...
查看详情
Vibration isolation and buffering of vehicle-mounted, ship-based, cabinet chassis, camera, drone and other equipment
Material: 304 stainless steel wire ...
查看详情
Vibration isolation and buffering of on-board photography, aerial photography, communication devices, electronic sensing equipment, mobile electronic instruments, surveillance cameras, rocker arms and other equipment
Material: The upper and lower plate...
查看详情
Electronic devices that need to be resistant to strong impacts
Material: Thickened steel plate, ch...
查看详情
I don't know how to solve the low-frequency vibration problem of the equipment. Please contact the vibration reduction engineer at sale@anlijing.com